Capacitor Bank Calculation Panel
![]() |
Capacitor Bank Panel |
This article explains the calculation of capacitor bank requirements to improve the power factor (cos φ) from 0.7 to 0.95 in a system with an installed power of 200 KVA.
Existing Data
Parameter | Symbol | Value | Unit |
---|---|---|---|
Power factor (cos φ) | cos φ | 0.7 | - |
Installed/Apparent power | S | 200 | KVA |
Active power | P | 140 | KW |
Reactive power | Q1 | 142.86 | KVAr |
Q1 = √(S² - P²) = √(200² - 140²) = 142.86 KVAr
Target to Achieve
Parameter | Symbol | Value | Unit |
---|---|---|---|
Power factor (cos φ) | cos φ | 0.95 | - |
Installed/Apparent power | S | 1730 | KVA |
Active power | P | 1643.5 | KW |
Reactive power | Q2 | 539.74 | KVAr |
Q2 = √(S² - P²) = √(1730² - 1643.5²) = 539.74 KVAr
Capacitor Bank Requirement (Qc)
To improve the power factor from 0.7 to 0.95, a capacitor bank with reactive power of:
Capacitor Distribution
The total capacitor requirement can be distributed in several configurations:
Configuration | Number of Capacitors | Power per Capacitor | Unit |
---|---|---|---|
Configuration 1 | 4 | 99.22 | KVAr |
Configuration 2 | 6 | 66.15 | KVAr |
Configuration 3 | 8 | 49.61 | KVAr |
Configuration 4 | 12 | 33.07 | KVAr |
For 6 capacitors: Qc/6 = 396.88/6 = 66.15 KVAr
For 8 capacitors: Qc/8 = 396.88/8 = 49.61 KVAr
For 12 capacitors: Qc/12 = 396.88/12 = 33.07 KVAr
Technician Class also provides a Capacitor Bank Calculator to make it easier for technicians to perform calculations.
Main MCCB Calculation
The following is the current (I) calculation for the main MCCB in various configurations:
Configuration | Capacitor Power | Current (I) | Unit |
---|---|---|---|
4 Capacitors | 99.22 | 150.83 | A |
6 Capacitors | 66.15 | 100.55 | A |
8 Capacitors | 49.61 | 75.41 | A |
12 Capacitors | 33.07 | 50.27 | A |
Example for 4 capacitors: (99.22 × 1000) / (380 × 1.73 × 1) = 150.83 A
Based on the above calculations, to improve the power factor from 0.7 to 0.95 in a system with an installed power of 200 KVA, a capacitor bank with a total reactive power of 396.88 KVAr is required. These capacitors can be distributed in several configurations according to needs and component availability.
The selection of the main MCCB should be adjusted to the chosen capacitor configuration, considering the current that will flow in each configuration.